PSU OPP BIM | Web Data | Asset Attribute Definition Table
Parameter Name |
Parameter Association | Asset Type | Description | Type | Max Characters or Format for Type | GUID |
Accessible | Room | Space Management | Yes or No; for new construction or major renovation this is typically "Yes"; Yes implies it meets current ABA standards at time of design/construction | YesNo | 3 | 2594330e-53eb-4792-a399-f665df0fa661 |
Actuated | Object | Operations | Has an actuated controller. (e.g. Manual control value would be NO, Actuated control valve would be YES) | YesNo | 3 | 6ec5ca29-2b55-4645-89df-64ffaaeca654 |
Alternative_Room_Name | Room | Space Management | Typically NOT used, however if the signage room name is different than the project this is where you track that information | Text | 200 | 0f4315b4-1eaf-459f-b02a-3452371e9c9b |
Alternative_Room_Number | Room | Space Management | Typically NOT used, however if the signage room name is different than the project this is where you track that information | Text | 200 | e5416b3b-7cd4-47d0-80ce-b0e3b86891d9 |
Amperage | Object | Operations | Total connected current (A) for the piece of equipment | Text | Revit Default | e928f742-bbd8-4222-b7f2-024afd70d7f8 |
Amperage_Motor | Object | Operations | If the motor is not a separate object, motor attributes should be included with the parent object | Numeric | Integer | 3a51df01-316c-404d-9f29-2ab5eaf970d1 |
Area | Room | Space Management | Square feet automatically calculated from Revit, in a Room this would be NSF, for a Roof it would be the surface area of the roof. | REVIT DEFAULT PARAMETER | Numeric | 0.xx | |
Area_Services | Project | Space Management | PSU OPP service area; see picklist "Service Area" for allowable entries; See picklist 'Service Area' and 'Value' column for the allowable entries | Text | 15 | da7d23f5-d177-4fc5-ae25-43685773b0af |
ASF_Type | Room | Space Management | Assignable Square Footage used for calculation/grouping of NSF; See picklist 'Room Type' and 'Alternative Value' column for the allowable entries | Text | 256 | 78b0614a-d5f0-4641-8485-10cf38c0e0d3 |
Assets | Room/Space | Operations | This is the total number of assets associated with the space that require maintenance over time. | Numeric | Integer | 281dccbc-e50f-4ac5-babf-3bb64e888a65 |
Associated_Asset | Object | Operations | Parent object using the "Equipment_ID" (e.g. a Motor inside of AHU-01 would list "AHU-01" here) | Text | Revit Default | c4589f3c-151b-4f91-a138-e367abbc96d0 |
Ballast_Details | Schedule Only | Operations | (Calculated) Automatically generated within a schedule as a combined parameter: | Text | Revit Default | 48c35970-e452-4f66-b5f0-8b132435d467 |
Barcode | Object | Operations | Maximo barcode applied to the piece of equipment | Text | Revit Default | d38dd0c1-5e83-4096-b78a-4e7e36935a51 |
BAS_Control_ID | Object | Operations | The building automation system / controls ID associated with the piece of equipment. Should match the controls plan documents | Text | Revit Default | e800ea7d-bf6a-4a4f-afa7-6229760912f4 |
Budget_Code | Room | Space Management | This comes from the Facility Coordinator and must be one of the valid PSU budget codes. | Text | 256 | 19ac451c-3a86-442c-b482-6c49a4844b58 |
Building Name | Project | Space Management | Parameter is at the Project Level (unless file includes multiple buildings) | REVIT DEFAULT PARAMETER | Text | 100 | |
Building_Count | Project | Space Management | Indicates whether or not the building should show in the PSU map; 0=No, 1=Yes (typically yes) | Numeric | 1 | 9eacce28-805c-4e11-9e94-a6bad103b10d |
Building_Function | Project | Space Management | Primary Building Category; See picklist 'Room Function' and 'Value Description' column for the allowable entries | Text | 256 | 367d9b85-73bf-4aa3-981e-a7d3f9ac1a42 |
Building_Function_Category | Project | Space Management | Primary Building Category; See picklist 'Room Function' and 'Value' column for the allowable entries | Text | 2 | 5db47999-7a86-4cef-9f91-22d9c4dbb3f5 |
Building_Lease_Code | Project | Space Management | Predominate lease code; Typically this is "Own" | Text | ?? | 94965ae3-5dd0-4637-9c18-a767e98f967e |
Building_Number | Project | Space Management | Building number | Text | 0000000 | 413a2113-8b1c-4766-9ef4-cd02561f38b6 |
Campus | Project | Space Management | See picklist "Campus Code" for allowable entries; See picklist 'Campus Code' and 'Value' column for the allowable entries | Text | 2 | 4e4f2ade-0784-4787-ba73-3b05c21121f8 |
Capacity | Object | Operations | Size, volume, or capacity of an item (e.g. 100 tons for a chiller). This is always paired with 'Capacity_UOM'. | Numeric | 0 | 3b0aedbe-c406-4f5a-bc45-60229d39824d |
Capacity_UOM | Object | Operations | Unit of measure (UOM) for the 'Capacity' attribute (e.g. BTU/HR, Tons, Gallons, etc.) | Text | 256 | 872d861d-6eda-452f-b74a-6ebc9eb672b5 |
CCT | Object | Operations | Correlated Color Temperature (CCT) | Text | 256 | b8c2f7a3-e51b-4de2-b3c7-b8bc70ca8f3d |
CFM | Object | Operations | Cubic feet per minute | Numeric | Integer | c8b306c0-ecf3-48ec-bfd9-1e8ab309fbb5 |
Circuit_Number | Object | Operations | Circuit within the panel to which the piece of equipment is connected | Text | Revit Default | c54af4cb-6ec5-4426-aa64-90404afb564a |
Closet_Connector | Object | ENCS | Network outlet connection type at the point of connection on the racks in the network closet; See picklist 'Network Connection' and 'Value' column for the allowable entries | Text | 1 | c13bc492-2dc7-47ba-9d13-ed92e1c21186 |
Coil_Capacity_Cooling | Object | Operations | Total cooling capacity of the asset/item (BTU/HR) | Numeric | 0.x | c7903565-620d-4bef-9e7f-73f492fdca75 |
Coil_Capacity_Heating | Object | Operations | Total heating capacity of the asset/item (BTU/HR) | Numeric | 0.x | 106815e6-b18a-4920-b8ee-d1ea341a8f7d |
Coil_Type | Object | Operations | Type of coil in the piece of equipment; See picklist 'Coil Type' and 'Value' column for the allowable entries | Text | 256 | dfca7985-e2f4-4a08-992f-2c646d8936f0 |
Coil_Type_Heating | Object | Operations | ?? | Text | 256 | c9051328-350d-439c-8879-438da0abea01 |
College_Primary | Project | Space Management | Predominate college user of the building | Text | 256 | 11f0ea9a-54d7-49d7-a4de-70b02927c3a9 |
Condition | Object | Operations | This is the condition of the item. Listed in picklist as "Condition:" + the Type of asset (e.g. Condition: Roof); See picklist 'Condition' and 'Value' column for the allowable entries | Text | 25 | d4a57404-5b13-488c-bb57-6bdd1750923a |
Condition_Code | Project | Space Management | This is the overall condition code for the building; Typically either "Excellent" or "Temporary" for projects at completion; See picklist 'Condition: Room' and 'Value' column for the allowable entries | Text | 25 | 36cb816f-f6f6-407e-852c-f5ab21a51b8b |
Controls | Object | Operations | Controls for item (e.g. lighting); See picklist 'Control' and 'Value' column for the allowable entries | Text | Revit Default | 7be4760c-d634-4d8a-8f4c-fbb93091926a |
Core | Object | Security | Door key core identifier | Text | Revit Default | 8a81268a-8ada-4eb8-80be-9c769b85af02 |
Count | Object | Operations | Used if listing a type of asset versus listing each individual of that type (e.g. 100 Lighting Fixture Type A's). If listing each asset individually it would be 1 | Numeric | Integer | 749e626b-c16a-49cf-aee4-78977e2a9e66 |
Decommissioned | Object | Operations | Items that are decommissioned should be listed indicating that they are to be removed / are removed. (e.g. Rooms or assets in a renovation project) | YesNo | 3 | b78b56d8-139e-4d9c-9d2d-483aa33fe002 |
Department | Room | Space Management | Free form text for users of the particular building for department naming convention they use (optional) | REVIT DEFAULT PARAMETER | Text | Revit Default | |
Description | Object | Operations | Free form text for additional descriptive information related to the asset | REVIT DEFAULT PARAMETER | Text | Revit Default | |
Dimming | Object | Operations | Luminaire dimming type | Text | 256 | 9ac8d4d9-3d5b-4500-a3cd-35b7beebdc70 |
Division_Code | Room | Space Management | See picklist 'Division Code' and 'Value' column for the allowable entries | Text | 256 | 1ac16a56-d919-4588-a27d-0b70e307e92a |
Donor | Room/Space | Space Management | This is the name if it has a special donor being recognized | text | 256 | 5530f3f2-3fc5-40a6-a195-b211edb5920e |
Drawing_ID | Object | Operations | Drawing set identification where the item is identified (e.g. M101, E101) | Text | Revit Default | 7c120ebe-922c-4e03-afd2-96bb4310bb4b |
Elevator_Number | Object | Operations | PSU elevator number; also required on the permitting documentation used with L&I | Text | 25 | c6b6cd6d-2e30-4852-9bed-ac816204a72c |
Emergency | Object | Operations | Item is on emergency power or part of the emergency egress planning; See picklist 'Yes No' and 'Value' column for the allowable entries | YesNo | 3 | 6f9e9ae0-a8af-4cd5-88af-6d1955167547 |
EnthalpyWheel | Object | Operations | Enthalpy wheel included | YesNo | 3 | da23f9fb-ca3b-4228-b80e-8dcc1d84bc4b |
Equipment_ID | Object | Operations | ID used for the piece of equipment instance or type. (e.g. AHU-01, Fixture A, etc.) Often is the same as the "Mark" or "Type Mark" field. Used as the Key for associating documents. | Text | Revit Default | 04c87bdc-abcb-46c9-9f27-191a1fd195c7 |
EWT | Object | Operations | Entering water temperature (°F) | Numeric | 0.0 | 3918ddd8-bd86-40e5-9556-ff435e1513ac |
Faceplate_Connector | Object | ENCS | Network connection type at the point of connection in the outlet box typically in a room or cubicle; See picklist 'Network Connection' and 'Value' column for the allowable entries | Text | 1 | ae74811a-ac29-4265-afb7-7d0c235e7c85 |
Filter_MERV | Object | Operations | ASHE Std 52.5 Minimum efficiency reporting value (MERV) rating for final filter | Text | 256 | 4f731527-f39c-43b4-b71d-fed15583f7c0 |
Filter_MERV_Pre | Object | Operations | ASHE Std 52.5 Minimum efficiency reporting value (MERV) rating for the pre-filter | Text | 256 | 77a0edb7-1ff7-4d0b-ad71-278ec680a14d |
Filter_Quantity | Object | Operations | Number of filters by size (e.g. If only one size of filter enter only quantity; if multiple filter sizes then enter quantity by size 20x24 @ 3, 30x36 @2) for the final filter | Text | 256 | c61ac93d-2f65-4c33-8c66-5c667e7076f9 |
Filter_Quantity_Pre | Object | Operations | Number of filters by size (e.g. If only one size of filter enter only quantity; if multiple filter sizes then enter quantity by size 20x24 @ 3, 30x36 @2) for the pre-filter | Text | 256 | b43859cc-a1ac-46e0-924c-e33f84fdbcbe |
Filter_Size | Object | Operations | Filter size(s) for any filters in the piece of the equipment for the final filter | Text | 256 | 5cbc9bea-b962-4198-9ffb-ff56ce525292 |
Filter_Size_Pre | Object | Operations | Filter size(s) for any filters in the piece of the equipment for the pre-filter | Text | 256 | f10c4f74-f88d-4d7f-96e2-5a69a260e4a5 |
Finish_Base | Room | Space Management | Finish material for the room base | Text | Revit Default | 601ac549-c45f-45d0-9300-37e8041d095f |
Finish_Ceiling | Room | Space Management | Finish material for the room ceiling | Text | Revit Default | 353aa385-8e02-43f5-96a5-27519356c610 |
Finish_Floor | Room | Space Management | Finish material for the room floor; See picklist 'Floor Finish' and 'Value Abbreviation' column for the allowable entries | Text | Revit Default | c52c1283-6685-403c-a99a-b6c42595f583 |
Finish_Wall | Room | Space Management | Finish material for the room walls | Text | Revit Default | 720b96bc-1732-43e2-84eb-58795404acf7 |
Fire_Rating | Object | Operations | Fire rating hours (e.g. Door with a 1 hour fire rating) | Numeric | Integer | 481d6796-b221-4add-90b6-bce043e69de7 |
Floor | Room | Space Management | This is the level or floor number without any descriptive text such as "Level" or "Floor" | Text | 2 | 35e54e6e-257b-4695-81f7-a3757cb661c1 |
FlowRate | Object | Operations | Fluid flow set point (gallons per minute GPM) | Numeric | 0.x | f9177d97-7f1b-4f9f-beaf-f2df79281efc |
FlowRate_Steam | Object | Operations | Steam flow rate in thousand BTU's per hour (MBH) | Numeric | 0.x | 9317da87-610d-4a5d-90aa-148426d78063 |
Fluid_ColdSide | Object | Operations | Fluid used on the cold side of a heat exchange; See picklist 'Fluid' and 'Value' column for the allowable entries | Text | 256 | 1b3535ef-0985-42de-a6f8-3e5e78f82f40 |
Fluid_HotSide | Object | Operations | Fluid used on the hot side of heat exchange; See picklist 'Fluid' and 'Value' column for the allowable entries | Text | 256 | 4c3313cf-879b-438d-8131-236dc2e91137 |
Frame | Object | Operations | Frame number | Text | Revit Default | a84114ff-1413-4b9e-8207-abcae98320a5 |
GSF | Area | Space Management | (Calculated) Gross square feet (GSF) | Numeric | 0.00 | 30991661-0e44-4625-944d-d1344c59aaad |
Handicap | Project | Space Management | Primary Building Category. See picklist for "Handicap" value field for allowable entries; See picklist 'Handicap' and 'Value' column for the allowable entries | Numeric | Integer | 5556a83e-731a-4886-9f92-28136b20ff8f |
Heat_Code | Project | Space Management | See picklist "Heat Code" for allowable entries; See picklist 'Heat Code' and 'Value' column for the allowable entries | Text | 20 | dba0a9f4-c17d-49f7-866f-9eb5f0f74b55 |
HeatPipe | Object | Operations | Heat pipe included; See picklist 'Yes No' and 'Value' column for the allowable entries | YesNo | 3 | 0c939fa2-c761-4978-8bab-a69eb0cdb71c |
Horsepower | Object | Operations | Horsepower (HP) | Numeric | 0.x | d03355ce-a3ff-4930-bbcf-3a621f668317 |
Horsepower_Motor | Object | Operations | If the motor is not a separate object, motor attributes should be included with the parent object | Numeric | 0.x | 13c5007e-9140-44cd-837a-90d23a6c3296 |
HX_DeltaT | Object | Operations | Hot side of a heat exchanger temperature drop from supply (inlet) to return (outlet) | Numeric | 0 | df800c66-4c74-4fbe-8458-d6d0d1510664 |
HX_EWT | Object | Operations | Entering water temperature. Hot side of a heat exchanger temperature on supply (inlet) side | Numeric | 0 | d7f2054c-f9d3-47fe-a3c6-c75af47a4938 |
HX_LWT | Object | Operations | Leaving water temperature. Hot side of a heat exchanger temperature on return (outlet) side | Numeric | 0 | c591dcb0-2991-4328-9bb0-2b2e31e94960 |
HX_Steam_EnteringPressure | Object | Operations | Entering steam pressure of a hot side of a heat exchanger using steam | Numeric | 0 | a61e7fad-2ac8-46f7-95ce-f5eb86123be0 |
Impeller_Diameter | Object | Operations | Pump impeller diameter (inches) | Numeric | 0.x | ca33966d-df47-4908-af14-3e5080420d75 |
Inlet_Size | Object | Operations | Inlet diameter size (inches) | Numeric | 0.x | 6689519e-f7f5-4077-b9a3-22f69f137c0b |
Installation_Date | Object | Operations | Date of installation | Date | YYYYMMDD | 2dd3bc34-8362-48ca-8bd4-3ce97f7bdae3 |
Interstitial | Room | Space Management | If the space is classified as a interstitial space then "Yes"; See picklist 'Yes No' and 'Value' column for the allowable entries | YesNo | 3 | 4f635fa3-83b0-4382-b28a-f5787dd18f7c |
Jack_Number | Object | ENCS | (Calculated) Concatenated field using "Building Number" + "-" + "Outlet" + "-" + "Media_Type" + "-" + "Network_Room" + "-" + "Port_Number"; See picklist 'Media Type' and 'Value Abbreviation' column for the allowable entries | Text | 1 | 81f10535-1b94-4974-bd12-441f14c0e482 |
Lamp | Object | Operations | Lamp description (e.g. T8); See picklist 'Lamp' and 'Value' column for the allowable entries | Text | 256 | 51c24668-ebd0-4598-82e7-eaf59dec6c0e |
Lamp_Details | Schedule Only | Operations | (Calculated) Automatically generated within a schedule as a combined parameter: | Text | Revit Default | a3c3c491-737c-45a7-8ce1-8866467dd177 |
Lamp_Life | Object | Operations | Expected hours of life for the lamp. For LED use lamp percentage of full and hours (e.g. "L80: 80,000") | Text | 256 | 42ead3d7-0e8d-49e7-be6e-770710eac5c3 |
Lamp_Quantity | Object | Operations | Number of lamps in the luminaire | Numeric | Integer | 58d474d3-6442-4ab9-887b-66f53e7b1ec2 |
Lamp_Style | Object | Operations | Luminaire lamp style | Text | 256 | a3b1fde5-a4f3-4494-ba17-bd8277757c56 |
Landings | Object | Operations | Total number of landings served by the item (e.g. Elevator serves 5 landings in a 4 story + basement building) | Numeric | Integer | 2369bc18-ab26-492a-8374-b4a86966b275 |
Lease_Code | Room | Space Management | This is typically "Own" | Text | 256 | 085bfe4a-c434-4cfd-bc06-3858c42e86c7 |
Level | System | Space Management | This is level or floor within the building | REVIT DEFAULT PARAMETER | Text | Revit Default | |
Lifecycle_Phase | Object | Operations | This is the phase of the of the data set. (e.g. Design, Construction, etc.); See picklist 'Lifecycle Phase' and 'Value' column for the allowable entries | Text | 256 | 1c3e593c-2558-4c68-a555-9c1f27ac5a08 |
Load_Max_UOM | Object | Operations | Unit of measure (UOM) for the 'Load' attribute (e.g. lbs, tons, psi, etc.) | Text | ?? | 4db73954-7f9d-404d-8076-02de26a04909 |
Load_Maximum | Object | Operations | Maximum load. Must specify the unit of measure (UOM) in "Load_UOM" | Numeric | 0.x | 6b3f44b6-8c46-4ff4-b654-ffb5f4616da0 |
Location | Schedule Only | Operations | (Calculated) Automatically generated within a schedule as a combined parameter: "Building Number" field + "-" + "Number" field | Text | 0000000-0xxx | 57a59ff5-635d-4249-82ed-98233a32f238 |
Lumens | Object | Operations | Fixture lumens | Numeric | Integer | 3c4afcec-b0fd-4cd8-b983-f32867f205e2 |
LWT | Object | Operations | Leaving water temperature (°F) | Numeric | 0.x | 501c169b-f825-4fad-b5e1-996c31af50ad |
Maintenance_Required | Object | Operations | The item requires some type of maintenance. Indicates a requirement for OM Manual(s); See picklist 'Yes No' and 'Value' column for the allowable entries | YesNo | 3 | 9c76f6c3-b8cd-42c4-8468-8c39315180c3 |
Manufacturer | Object | Operations | Manufacturer of the item/asset | Text | Revit Default | 275d4593-78ff-44ac-9397-0175748f2945 |
Manufacturer_Motor | Object | Operations | If the motor is not a separate object, motor attributes should be included with the parent object | Text | Revit Default | e76454ca-6404-401d-8c6c-c9d20e95fa15 |
Mark | Object | Operations | Asset type mark used to identify an instance of the object (e.g. AHU-01) | REVIT DEFAULT PARAMETER | Text | 256 | |
Mark Type | Object | Operations | Asset type mark used to identify the object (e.g. lamp Type A) | REVIT DEFAULT PARAMETER | Text | ?? | |
Material_of_Construction | Object | Operations | Material of construction for the asset (e.g. Copper). Picklist as "Material of Construction:" + the Type of asset (e.g. Material of Construction: Roof); See picklist 'Material of Construction' and 'Value' column for the allowable entries | Text | 250 | 39f03f1b-4378-423b-a627-c82f5f910f24 |
Maximo_Name | Room/Space | Space Management | Name to be used in CMMS (Maximo) | Text | 35 All CAPS |
aa176f3c-7f36-4e45-a7f8-8c60c1795bec |
Media_Type | Object | ENCS | Type of cable used; See picklist 'Media Type' and 'Value Abbreviation' column for the allowable entries | Text | 1 | f3275172-9995-42db-aaf4-97760d71a12a |
Model | Object | Operations | Model, Manufacturer Catalog Number, etc. of the item/asset | Text | Revit Default | dafb267f-f0af-455b-aa78-8fbf82552be9 |
Model_Motor | Object | Operations | If the motor is not a separate object, motor attributes should be included with the parent object | Text | Revit Default | e3e17d13-ae38-447f-ac27-d3ed18c25e20 |
Name | Room/Space | Space Management | Room name; system default field | REVIT DEFAULT PARAMETER | Text | 256 | |
National_Board_Number | Object | Operations | National board of boiler and pressure vessel number | Text | 256 | ff31f9e9-24c7-44bd-a927-2925eef47a79 |
Network_Room | Object | ENCS | Network room for the building (e.g. A, B, C, etc.); See picklist 'Network Room' and 'Value Abbreviation' column for the allowable entries | Text | 1 | 43abb05c-7baf-4548-8ebc-db2bc62e0954 |
Nominal_Voltage | Object | Operations | Nominal voltage associated with the asset | Text | Revit Default | c577dd8a-1e21-44b8-9287-b954e4777aa9 |
Number | Room/Space | Space Management | Room number using PSU's room numbering standard | REVIT DEFAULT PARAMETER | Text | 25 | |
Occupancy | Room | Space Management | Current Room capacity: Total count of seats in the space; for an office it would be the occupant; for classroom it would be same as student seats + instructor(s) | REVIT DEFAULT PARAMETER | Numeric | Integer | |
Official_Name | Room | Space Management | This is an official name given to the room (e.g. donor, in honorary, etc.) | Text | Revit Default | 96336741-5ff8-4ef1-83b8-aa97f73e6625 |
OM_Manual_Number | Object | Operations | Operations and maintenance manual number associated with the item | Text | 250 | 495e6a93-32de-4783-b343-bbb291334272 |
OMManual_Required | Object | Operations | Indicates whether or not the item/asset requires an operations and maintenance (OM) manual; See picklist 'Yes No' and 'Value' column for the allowable entries | YesNo | 3 | e803493f-f227-46d6-aad2-1ff5c3bb9f46 |
Outlet | Object | ENCS | Network/Communication outlet box typically in room or cubicle | Text | 0000 | 6e04c647-69ce-46fd-af71-be0bc1043f4c |
Ownership_Status | Project | Space Management | Identifies the ownership classification of the building/project area.; See picklist 'Ownership Status' and 'Value' column for the allowable entries | Text | 10 | 38d2439b-4ec9-4e70-a987-09b496750598 |
Panel | Object | Operations | Power panel to which the piece of equipment is connected | Text | Revit Default | f5b4a7c7-1e52-464e-ab1a-47fdeacfaac0 |
Permit_Required | Object | Operations | Permit is required (e.g. L&I, county, local, PSU); See picklist 'Yes No' and 'Value' column for the allowable entries | YesNo | 3 | ee833fdc-076c-4598-8fdd-53b22c5664d1 |
Phases | Object | Operations | Number of phases for the asset | Text | Revit Default | 80dd9884-2568-4c00-afb1-ef2f470ccb2c |
Phases_Motor | Object | Operations | If the motor is not a separate object, motor attributes should be included with the parent object | Numeric | Integer | fd0a99a7-9e87-4b56-ac08-63f208d94502 |
Port_Number | Object | ENCS | Port/Jack within the outlet; PSU allows up to 6 jacks per network/communication outlet | Text | 0000 | 6960db3e-9f3b-4ac3-9ac4-ab170e88a096 |
Pressure_Drop | Object | Operations | Pressure drop in feet of water (FT H2O) in the asset (e.g. on the hot side of a heat exchanger) | Text | 256 | 31f6e661-5278-41ed-b4e5-feaefbb82de9 |
Pressure_Head_Design | Object | Operations | Design pressure head in feet of H20 | Numeric | 0.x | e9d1b0d2-49c4-498a-99ae-31351e32abdb |
Project Name | Object | General | Project Name used by contractor (designer, builder, etc.) | REVIT DEFAULT PARAMETER | Text | Revit Default | |
Project Number | Object | General | Project Number used by contractor (designer, builder, etc.) | REVIT DEFAULT PARAMETER | Text | Revit Default | |
Project_Name | Object | General | PSU Project Name | Text | 256 | 2a0d193e-fc95-4f0d-9053-b188445205e7 |
Project_Number | Object | General | PSU Project Number | Text | 000000000 | 3cf653c1-3365-48e1-b4d1-b9c3c42afbfc |
Refrigerant_Charge | Object | Operations | Amount of regrigerant loaded into the system/asset/item | Text | 256 | b5b40de8-49c8-4de4-a307-df1d4ea84a39 |
Refrigerant_Type | Object | Operations | Type of refrigerant used in the item/asset; See picklist 'Refrigerant' and 'Value' column for the allowable entries | Text | 256 | 695bb2db-9b9e-46dd-bdef-ab15bc287fea |
Room_AC | Room | Space Management | See picklist 'Room AC' and 'Value' column for the allowable entries | Text | 1 | 894c985d-af21-493b-9155-165780a13807 |
Room_Condition | Room | Space Management | Typically either "Excellent" or "Temporary" for projects at completion; See picklist 'Condition: Room' and 'Value' column for the allowable entries | Text | 25 | fa555e9b-4c45-471e-ad11-6233ca35bc0f |
Room_Function_Code | Room | Space Management | See picklist 'Room Function' and 'Value' column for the allowable entries | Text | 00 | 75ce8ffb-d299-446f-9fec-65ae5d9e9ff8 |
Room_Function_Description | Room | Space Management | See picklist 'Room Function' and 'Value Description' column for the allowable entries | Text | 256 | e8b53e82-a13c-452c-a64c-27a92a883443 |
Room_ID | Schedule Only | Space Management | (Calculated) Automatically generated within a schedule as a combined parameter: "Building_Number" + "-" + "Floor" + "Number" | Text | 0000000-0x-0xxx | 673e7b2f-278b-4600-9b37-0dbc661090c5 |
Room_Type_Code | Room | Space Management | See picklist 'Room Type' and 'Value' column for the allowable entries | Text | 000 | 969d36fa-1a88-44c7-bff1-2ce85d9e8ffa |
Room_Type_Description | Room | Space Management | See picklist 'Room Type' and 'Value Description' column for the allowable entries | Text | 256 | bf1083c2-182a-404e-888f-bf2b3bef579a |
RPM | Object | Operations | Revolutions per minute | Numeric | Integer | 4cfe0cb4-c5fc-4c15-8216-29c36c3acc99 |
RPM_Motor | Object | Operations | If the motor is not a separate object, motor attributes should be included with the parent object | Numeric | Integer | c42a2e72-0fe7-4feb-bc1f-a56b2201ee51 |
Security_Door | Object | Security | Security control type for the door; See picklist 'Security Door' and 'Value' column for the allowable entries | Text | Revit Default | e0fa47e1-0622-43ae-8e66-4bd92c50f59e |
Security_Room | Room | Security | Security consideration type for the room; See picklist 'Security Room' and 'Value' column for the allowable entries | Text | Revit Default | 26fa09b8-afbf-4a69-8b01-598397080b62 |
Serial_Number | Object | Operations | Serial number for the item/asset | Text | Revit Default | b71c21fb-0e3e-41ce-afa9-431a266a0f2d |
SetPoint_Flow | Object | Operations | Fluid flow set point (gallons per minute GPM) | Numeric | 0.x | 3fa3e03b-d296-454f-9431-9fb53c7802b2 |
SetPoint_Temperature | Object | Operations | Temperature setpoint (°F) | Numeric | 0.x | 46874ea3-13a5-4720-99aa-3019fc20dc9f |
Short_Name | Project | Space Management | This is an abbreviated name for the building | Text | 50 | abcdf2a8-f5bb-41b1-a0e9-b1882281c072 |
Space_Served | Object | Operations | Space(s) served by the piece of equipment | Text | Revit Default | 1391948a-98d5-4617-8d4e-8524d0840e66 |
Speed | Object | Operations | Speed of the item (e.g. elevator speed) | Numeric | 0.x | ea81de58-aa24-4179-a860-30102a3638c3 |
Speed_UOM | Object | Operations | Unit of measure for the 'Spee' attribute (e.g. for an elevator speed 'FPM') | Numeric | 0.x | 0662be72-0240-47ab-b191-ab63cd4a1398 |
Student_Seats | Room | Space Management | Total count of seats available for students | Numeric | Integer | f4410fcf-c275-42ff-95c7-f439a37a5daa |
Submittal_Number | Object | Operations | Submittal number associated with the item (final is approved submittal not interim submittals) | Text | 250 | ce2bcdc7-d6c0-47e5-8dc3-6a5059840ca7 |
Submittal_Required | Object | Operations | Indicates whether or not the item/asset requires a submittal; See picklist 'Yes No' and 'Value' column for the allowable entries | YesNo | 3 | 7dd3a556-8fea-4012-b270-0615b539740e |
Substantial_Completion_Date | Project | Space Management | This is the date of substantial completion | Date | YYYYMMDD | c4dbdb87-ea63-4e9e-95ff-965d8ac8c30b |
SubSystem | Object | Operations | Omni-Class System (Level 3) ; See picklist 'Building System Type' and 'Value' column for the allowable entries | Text | Revit Default | 8edb455c-1e12-49a0-be71-f5ef156113ae |
SubType | Object | Operations | Sub type of asset. Sub type group is listed in picklist as "Asset Type:" + the Type of asset (e.g. Asset Type: Fan); See picklist 'Asset Type' and 'Value' column for the allowable entries | Text | Revit Default | ef1f7196-3652-45c6-b2e1-08ed56be937c |
Supply_Air_Temperature | Object | Operations | Air temperature supplied by the item | Numeric | 0.x | a31bfdf3-ffdb-4487-935f-505cd5ee85ca |
Supply_Air_Temperature_SetPoint | Object | Operations | Set point / target temperature supplied by the item | Numeric | 0.x | 87162de4-d45b-4269-b95a-b492970467e8 |
System | Object | Operations | Omni-Class System (Level 2) ; See picklist 'Building System' and 'Value' column for the allowable entries | Text | Revit Default | 193f2696-9ef0-4b3e-8de1-10aab2d18942 |
Type | Object | Operations | Type of asset; See picklist 'Asset Type' and 'Value' column for the allowable entries | Text | Revit Default | 88e3d7b9-463e-4fa1-9be2-5864126ab00c |
URL_ApprovedSubmittal_Doc | Object | Operations | This is the URL for asset's associated approved submittal (AS) document | URL | 256 | c9081e0b-cae0-4819-a563-15ecc2acb387 |
URL_CxReport_Doc | Object | Operations | This is the URL for asset's Commissioning (Cx) Report document | URL | 256 | 79a4e8d5-92c2-4a44-a2ef-dfd9373a17d3 |
URL_NamePlate_Pic | Object | Operations | This is the URL for asset's picture of the name plate | URL | 256 | 4804acd2-f10c-4a77-921f-5634c16515c7 |
URL_OMManual_Doc | Object | Operations | This is the URL for asset's operations and maintenance (OM) manual document | URL | 256 | 14133474-b3a8-4e1d-a6a0-783e13fc758b |
URL_Permit | Object | Operations | URL for the associated permit documents | Text | 256 | ce780440-79b6-468a-a627-0937cd009a55 |
URL_PSU_BOX | Project | Operations | This is the URL for the project on PSU's BOX where deliverables will be provided | URL | Revit Default | a26f7123-158c-491f-b3ec-8bc8e4516e2c |
URL_TAB_Doc | Object | Operations | This is the URL for asset's Testing, Adjusting, Balancing (TAB) Report document | URL | 256 | c2545184-8018-486b-b323-f006b036c342 |
URL_Warranty_Doc | Object | Operations | This is the URL for asset's warranty (W) document | URL | Revit Default | 60868ee0-213b-4ff8-b7f8-339bab47bc12 |
VFD | Object | Operations | Includes a variable frequency drive; See picklist 'Yes No' and 'Value' column for the allowable entries | YesNo | 3 | 1537e7f8-25df-4ecb-b9f9-40680d53e876 |
VFD_AirFilter | Object | Operations | The vraible frequency drive (VFD) includes an air filter; See picklist 'Yes No' and 'Value' column for the allowable entries | YesNo | 3 | e679a34a-2b5d-4c8e-8839-005970941e83 |
Voltage | Object | Operations | Primary voltage for a piece of equipment | REVIT DEFAULT PARAMETER | Text | Revit Default | |
Voltage_Ballast | Object | Operations | If the ballast is not a separate object, motor attributes should be included with the parent object | Text | 256 | 06959d0a-9fdf-45cc-8fd5-0d5ad5290fd5 |
Voltage_Motor | Object | Operations | If the motor is not a separate object, motor attributes should be included with the parent object | Text | Revit Default | c749c9cc-0d2f-4afa-a54e-9c01cf6be7ea |
Voltage_Secondary | Object | Operations | Secondary voltage for a piece of equipment if more than one exists | Text | Revit Default | ff571b54-97cd-4629-b860-759b9234d821 |
Warranty_End_Date | Object | Operations | The date the equipment warranty ends for PSU OPP | Text | Revit Default | 387ae842-24b2-4484-a7f6-0a8e1ece6021 |
Wattage | Object | Operations | Wattage for the piece of equipment (e.g. for a light fixture it would be the total Luminaire watts) | Numeric | 0.xx | cd81427e-4759-489f-b6aa-5c666e31cf6e |
Wattage_Lamp | Object | Operations | Wattage for the luminaire lamp(s) | Numeric | Integer | 8deb339c-1c37-4760-b8fe-5ad9b39ad50a |